1.technical performance
● to subject: liquid, gas or vapour
● range ability:
LU-CDPS-3300 LU-CDPS-5300 LU-CDPS-5400 LU-CDPS-5500 LU-CDPS-6400 LU-CDPS-6500 |
0~1.2~7.2KPa 0~1.2~7.2KPa 0~6~36KPa 0~30~180KPa 0~6~36KPa 0~30~180KPa |
● output: 4-20mA DC
● power: 24VDC, it may be 12VDC if non-load, max. is 45VDC
● positive & negative transfer: up and low may not exceed the range limit after positive & negative transfer, whatever the output is.
Max. positive transfer: 500% of the min. span.
Max. negative transfer: 600% of the min. span.
·Temperature:
temperature of operating for amplifier:
temperature of operating for sensor:
·Relative humidity: 0~100%
·Sensor capacity changes: <0.16cm3
·Indicate meter (field): scale gauge length: 30mm,
grade: 2.5
·Isolating explosion: ds Ⅱ BT5, Intrinsically-safety: ia Ⅱ CT5
·Span & Zero: external continually adjusted
·Static-pressure and Over-pressure limit:
if add 0 (absolute pressure) –14Mpa to any side of the transmitter, no damage for transmitter
·Static-pressure affect:
zero error: ±0.5% of max. range, when rated operating pressure
range error: pressure is±0.5%, this is a system error, may calibrate and eliminate the error according to actual static pressure before mounting.
·Damp: continually adjusted when time constant is between 0.2~1.67 seconds.
·Settling time: 2s,
2. performance index (note: test under the condition of none shift, max. range status of sensor,
·Accuracy: ±0.25% of the span, including the synthesize errors of linear, change-difference and repeat.
·Stability: ±0.25% of max. range (12 months)
·Temperature affect:
zero error:±0.5% /
zero error:±3.0% /
·Over-pressure affect: ±0.25% of max. range (according to permitted over-loads for different ranges)
·vibration affect: ±0.05% / g of the max. range, when 200Hz, any axis up.
·Power affect: <0.005%/V of output range
·Load affect: none affect when voltage >12VDC input to the transmitter.
·Mounting position affect: may cause zero error max. 0.24Kpa, but can be calibrated.
3. structure index:
·Structure material: diaphragm: 316 stainless steel, hastelloy C, Monel alloy, Tantalum;
O ring: Fluorin rubber;
Flange & bolt: 316 stainless steel;
Fill oil: silicon oil;
Electric shell: low-Cu & aluminum alloy
Plating of electric shell: toast lacquer of amido, formyl, ethene & colophony;
·pressure-lead connector:
flange NPT 1/4 (taper pipe screw thread), (this is the transmitter flange connection);
connection head screw thread NPT 1/2 (taper pipe screw thread), (selected);
·electric parts connector:
down-lead conduit NPT 1/2 line-through hole;
·net weight: 2.4kg (exclude the selected parts)