Safety Barriers
Product Details · PRODUCT DETAILS
LU-B11 Operation-End (Signal Output) Isolation Safety Barrier (1 In / 1 Out)
The LU-B11 operation-end (signal output) isolation safety barrier connects a variety of DC signals below 20mA or 10V. It receives DC voltage signals from a DCS/PLC system or other operator in the safe area, transmits them through the isolated barrier, and outputs the required DC current or voltage signal to drive I/P converters, valve positioners, display devices and other intrinsically safe instruments in the hazardous field. An independent power supply provides isolation between supply, input
I. Overview
● The LU-B11 safety barrier can be connected to a variety of DC signals of less than 20mA or less than 10V.
● Receives DC voltage signals from DCS/PLC systems or other operators located in the safe area, transmits them isolated through the safety barrier, and outputs the required DC current or voltage signal to drive intrinsically safe instruments in the hazardous field, such as electro-pneumatic converters, valve positioners and display devices.
● Powered by an independent power supply, with isolation between power supply, input and output.
II. Technical specifications
● Input parameters (safe-area signal)
For current input Input range: 4~20mA
Input resistance: built-in input resistor 100Ω
For voltage input Input range: 1~5V, 0-5V, 0-10V
Input resistance: >500KΩ
● Output parameters (hazardous-area signal)
For current output Output range: 4~20mA
Permissible load: ≤750Ω
For voltage output Output range: 1~5V
Built-in resistor: 250Ω
Output impedance: ≤500Ω
● Intrinsic safety parameters
Explosion-proof marking: [Exia]ⅡC
Maximum voltage Um: 250V
Maximum output voltage Uo: 28V
Maximum output current Io: 93mA
Maximum external inductance Lo: 2.4mH
Maximum external capacitance Co: 0.05μF
● Ambient parameters
Power sup ply: 20-30VDC
Ripple factor below 10%P-P, approx. 1W
Power indicator lamp: green LED, lit when the power is supplied
Operating temperature range: -20~ +60°C
Operating humidity range: 0 ~ 95%RH (non-condensing)
● General technical parameters
Standard accuracy: ±0.1%
Temperature drift: ±0.015%/°C
Response time: ≤10mS
Insulation resistance: 2.5KV, 1min, 50HZ between input, output and power supply
Isolation strength: input-output-power supply ≥100MΩ/500VDC
Effect of load resistance variation: ±0.1%/250Ω (for current output)
±0.1% (for voltage output)
Power-on stabilization time: ≤3s
LU-B11 Operation-End (Signal Output) Isolation Safety Barrier (1 In / 1 Out) Selection Guide
Click to download the product manual. If the download fails, please contact customer service.
Related Products
Need technical specifications and a quotation for this product?
Submit your request and our engineers will contact you within one business day.