Safety Barriers

Product Details · PRODUCT DETAILS

LU-BK11 Digital Output Isolation Safety Barrier (1 In / 1 Out)

The LU-BK11 safety barrier controls field devices in the hazardous area via switch, transistor or logic-level signal input from the safe area, and is suitable for driving solenoid valves, alarms and other intrinsically safe devices without energy storage. It is powered by an independent DC supply with isolation between supply, input and output, and includes high/low output status indicators. The compact, lightweight design allows high-density installation.

  • CategorySafety Barriers
  • Model-
  • Views8160 views
  • Updated2011-11-25
Selection customization and technical solution support available. After-sales Service 0086-400-8875-999, Pre-sales Hotline 0086-0592-5711111

I. Overview

A. Main functions and features

●The LU-BK11 safety barrier controls field devices in the hazardous area by switching the safe-area power supply through switch, transistor or logic level signal inputs. It is suitable for driving intrinsically safe devices such as solenoid valves and alarms, as well as other simple devices without energy storage.

● Powered by an independent DC power supply, with isolation between power supply, input and output.

● Equipped with an indicator for the high/low level status of the output signal

● Compact and lightweight, allowing high-density installation

II. Technical specifications

● Input parameters (safe-area signal)

Input type   

A.  Dry contact switch selected: input current  ≤3mA / 24V;  switch delay ≤2s

B.  Level signal selected: high level 4~24V; low level ≤1V C.  Transistor selected: electrical rating  30VDC, 100mA

● Output parameters (hazardous-area signal)

Output signal:  logic voltage signal

Output equivalent circuit (Figure 1):

Output characteristic curve (Figure 2):

Minimum output voltage: 12V at 45mA

Maximum output voltage: 24V

Maximum output current: 45mA

● Input and output characteristics

Normal phase (*Note: the description in brackets refers to the reverse phase)

A. Dry contact switch selected: if the input switch is closed, the output conducts and the yellow output indicator lights up

B. Level signal selected: if the input is a high level of 4~24V, the output conducts and the yellow output indicator lights up.

C. Transistor selected: if the input transistor is conducting, the output conducts and the output indicator yellow lamp lights up.

(In reverse phase, it does not conduct and the output indicator yellow lamp goes out)

A. If the input switch is open, the output does not conduct and the output indicator yellow lamp is off

B. If the input low level is <1V, the output does not conduct and the output indicator yellow lamp is off.

C. If the input transistor is not conducting, the output does not conduct and the output indicator yellow lamp is off.

(In reverse phase, it conducts and the output indicator yellow lamp lights up)

*Note : if reverse phase is required, it must be set via the internal micro switch of the product; please specify this when ordering.

● Intrinsic safety parameters

Explosion-proof marking: [Exia] ⅡC

  Maximum permissible voltage Um: 250V

  Maximum open-circuit voltage Uo: 25V

Maximum short-circuit current Io: 147mA

Maximum external inductance Lo: 1.4mH

Maximum external capacitance Co: 0.08μF

● Ambient parameters

Power sup ply: 20-30VDC

Power indicator lamp: green LED, lit when the power is supplied

Current consumption (with 24VDC power supply): single channel < 75mA (at output current 45mA);  

  Operating temperature: 0~ +50 °C

Storage temperature: -20~ +60°C

Relative humidity: 0 ~ 95%RH (non-condensing)

● General technical parameters

Standard accuracy: ±0.1%

Temperature drift: ±0.015%/°C

Response time: ≤10mS

Insulation resistance: 2.5KV, 1min, 50HZ between input, output and power supply

Isolation strength: input-output-power supply ≥100MΩ/500VDC

Power-on stabilization time: ≤3s

LU-BK11 Digital Output Isolation Safety Barrier (1 In / 1 Out) Selection Guide

Click to download the product manual. If the download fails, please contact customer service.

Download Now
RELATED PRODUCTS

Related Products

View Related Products

Need technical specifications and a quotation for this product?

Submit your request and our engineers will contact you within one business day.