Safety Barriers
Product Details · PRODUCT DETAILS
LU-AK22 Digital Input Isolation Safety Barrier (2 In / 2 Out)
The LU-AK22 safety barrier receives switch contact or proximity sensor signals from the hazardous area and, after isolation, transmits them to control systems or other panel instruments in the safe area via relay contact (level signal or transistor) outputs. It is powered by an independent DC supply with isolation between supply, input and output.
I. Overview
●The LU-AK22 safety barrier receives switch contact or proximity sensor signals from the hazardous area, isolates them through the safety barrier, and transmits them to the control system or other combined instruments in the safe area by relay contact (level signal or transistor) output.
●The isolating safety barrier is powered by an independent DC power supply, with isolation between power supply, input and output.
II. Technical specifications
● Input parameters (hazardous area signals)
◆Input type:
The passive input is a pure switch contact; the NAMUR type is a proximity sensor conforming to the DIN19234 standard.
Active signal: when the input signal is > 2.1mA, it is indicated as “ON”
When the input signal is < 1.2mA, it is indicated as “OFF”
Open-circuit voltage: 8V±0.5V Short-circuit current: approx. 4mA
Switching threshold: approx. 1.55mA Hysteresis: 0.2~0.4 mA
●Output parameters (safe area signals)
◆Output type:
A. Relay contact: single-pole changeover relay
Contact rating: 24VDC, 2A ; Load type: resistive load; Response time: ≤10ms
B. Level signal: high level 4.5V ~ 5.5V ; low level ≤0.5V ; high-level drive capability≤20mA
C. Transistor: external supply voltage ≤40V; drive output current≤40mA
Transistor collector output High level: VCC; Low level: ≤2.5V
Transistor emitter output High level: VCC -2.5V; Low level:≤ 0.5V
● Intrinsic safety parameters
Explosion-proof marking: [Exia] ⅡC
Maximum permissible voltage Um: 250V
Maximum open-circuit voltage Uo: 11V
Maximum short-circuit current Io: 15mA
Maximum external inductance Lo: 10mH
Maximum external capacitance Co: 1.4μF
Ambient parameters
Power sup ply: DC24V±10%
Current consumption (with 24VDC power supply): <50mA
Power indicator lamp: green LED, lit when the power is supplied
Output indicator lamp: yellow LED, contact status indication; OUT1 indicates the first output, OUT2 indicates the second output
“OUT” lamp on: indicates that the contact is in the closed state
“OUT” lamp on: indicates that the contact is in the open state
Operating temperature range: -20~ +60°C
Operating humidity range: 0 ~ 95%RH (non-condensing)
● General technical parameters
Standard accuracy: ±0.1%
Temperature drift: ±0.015%/°C
Response time: ≤10mS
Insulation resistance: 2.5KV, 1min, 50HZ between input, output and power supply
Isolation strength: input-output-power supply ≥100MΩ/500VDC
Power-on stabilization time: ≤3s
LU-AK22 Digital Input Isolation Safety Barrier (2 In / 2 Out) Selection Guide
Click to download the product manual. If the download fails, please contact customer service.
Related Products
LU-BK11 Digital Output Isolation Safety Barrier (1 In / 1 Out)
View Details
LU-AK12 Digital Input Isolation Safety Barrier (1 In / 2 Out)
View Details
LU-AK11 Digital Input Isolation Safety Barrier
View Details
LU-AB22 Detection-End + Operation-End Isolation Safety Barrier (2 In / 2 Out)
View DetailsNeed technical specifications and a quotation for this product?